Current Transformer 1:1500 , 10A/6.66mA

Type : Current transformer

FULLSTAR P/N: CT21FC10A-6.66mA 


Working principle 

Principle of current transformer is based on the principle of electromagnetic induction. The current transformer is composed of a closed iron core and a winding. The primary winding turns is less and connected in series in the circuit to measure the current, so it often flows all current in circuit; Secondary has more windings and connected in series of measuring and protection circuit. When current transformer is in operation, the two- loop is always closed. Therefore, measuring and protecting loop-circuit impedance in series with the coil current transformer is very small, close to the state of short circuit.


Specs

Turns Ratio: 1:1500 

Rated pri current: 10A  

Rated sec current: 6.66mA 

Output voltage: 100mv+/-10%@15A , RL=10Ω 

Accuracy: 0.5%

Inductance: 42H Min@100Hz, 0.1V 

DCR: 175Ω MAX 

Hi-pot: 2.5KV,1mA, 1Min 

Insulation resistance: 500Vdc,100MΩ Min

Operating temperature: -20℃ to +70℃

Storage temperature: -40℃ to + 85℃


Note:

1. RoHS Compliant

2. Flammability: UL94V-0

3. ASTM oxygen index: >29% 

4. Temp 20℃, 48%RH 


Dimension 

1500 current transformer


Testing report


Sample show 

10A/6.66mA current transformer


We also produce other transformers 


Encapsulated transformer / balun transformer / Switching power transformer / LAN transformer 



CONTACT INFO  :

QQ:  1478124633

Skype: sophie84_2005116

Wechat : 55911767 

WhatsApp: 15829062422 

TEL: 86-29-86676405 / 

      15829062422/ 18192289495

Mail: sales@xfullstar.com